Interactive Cables

0.6/1kV 1CX70mm2 CU C5MG/X-HF-110/HFS-110-TP RD

Fire Rated Single Core Power Cables

0.6/1kV 1CX70mm2 CU C5MG/X-HF-110/HFS-110-TP RD

Product Standard AS/NZS 5000.1
Performance Standard(Flame / Fire – Test) AS/NZS 3013
Rated Voltage(Uo/U) 0.6/1 kV

1 Circular Stranded Copper Class 5 Conductor
Number of Core(s) 1 Nos
Nominal cross-sectional area 70 mm2
Approx. Diameter of Conductor 11 mm
2 Insulation – MGT + X-HF-110
Color(s) RED
Nominal Thickness 1.1 mm
Approx. Diameter over Insulation 14.5 mm
3 Extruded LSZH Outer                                Sheath (RED)
Nominal Thickness 1.41 mm
Approx. Diameter over outer sheath 18 mm
4 Approx. Weight of complete cable 841 kg/km
5 Electrical Parameters
Max. DC Resistance of Conductor at 20°C 0.272 Ω/km
Approx. AC Resistance of Conductor at 110 °C 0.369 Ω/km
Approx. Capacitance 0.739 μF/km
Approx. Inductance 0.25 mH/km
Approx. Inductive Reactance 0.103 Ω/km
Approx. Impedance 0.36 Ω/km
6 Current Carrying Capacity based on the conditions specified
Installation Type (Single Circuit) Trefoil Both ends bonded
Ambient air temperature 30 °C

In air 268 Amps
7 Maximum conductor temperature for continuous operation / 110/250 °C
Short Circuit Operation
8 Short Circuit Current carrying capacity, cable loaded as above prior to short circuit
Conductor 9.23 kA/1 sec
9 Installation Parameters
Maximum pulling force (For Conductor) 420 kgf
Minimum Bending Radius 144 mm