Product Standard AS/NZS 5000.1
Performance Standard(Flame / Fire – Test) AS/NZS 3013
Rated Voltage(Uo/U) 0.6/1 kV
1 Circular Stranded Copper Class 5 Conductor
Number of Core(s) 1 Nos
Nominal cross-sectional area 10 mm2
Approx. Diameter of Conductor 4.2 mm
2 Insulation – MGT + X-HF-110
Color(s) RED
Nominal Thickness 0.7 mm
Approx. Diameter over Insulation 6.7 mm
3 Extruded HFS-110-TP Outer Sheath (RED)
Nominal Thickness 1.4 mm
Approx. Diameter over outer sheath 10.2 mm
4 Approx. Weight of complete cable 188 kg/km
5 Electrical Parameters
Max. DC Resistance of Conductor at 20°C 1.91 Ω/km
Approx. AC Resistance of Conductor at 110 °C 2.586 Ω/km
Approx. Capacitance 0.501 μF/km
Approx. Inductance 0.28 mH/km
6 Current Carrying Capacity based on the conditions specified

Installation Type (Single Circuit) Trefoil Both ends bonded
Ambient air temperature 30 °C
In air 81 Amps
7 Maximum conductor temperature for continuous operation / 110/250 °C
Short Circuit Operation
8 Short Circuit Current carrying capacity, cable loaded as above prior to short circuit
Conductor 1.32 kA/1 sec
9 Installation Parameters
Maximum pulling force (For Conductor) 60 kgf
Minimum Bending Radius 82mm